Single-phase Hybrid Inverter (3kW / 3.6kW / 4kW / 5kW / 6kW)

  • Stable: fanless design to prolong lifespan; full auto-protection
  • Flexible: Retrofit function and easy to expand
  • Easy use: remotely control and upgrade function
  • Smart UPS: smart LCD display; plug & play, seamless switching under 20 ms; sufficient backup power for emergency use
  • Intelligent EMS function, improving battery’s reliability
  • Easy to use with battery: higher charging and discharging current; compatible with lithium and lead-acid batteries
SKU: HBH-S3~6K Categories: ,
Technical DataHBH-S3KHBH-S3.6KHBH-S4KHBH-S5KHBH-S6K

Input DC (PV side)

Recommended maximum PV power7kW10kW
Start-up voltage100V
Maximum input voltage600V
Rated voltage330V
MPPT voltage range90V~520V
Maximum input current20A / 20A
Maximum short circuit current30A / 30A
Number of MPPT / Strings per MPPT2/2

Battery

Battery typeLithium / Lead-acid
Battery voltage range42V~58V
Battery capacity50Ah~2000Ah
Maximum charge/discharge power3kW3.6kW5kW
Maximum charge/discharge current62.5A100A
CommunicationCAN

Output AC (Back-up)

Rated output power3kW3.6kW4kW5kW6kW
Maximum apparent output power4.5kVA, 10 sec7kVA, 10 sec
Back-up switch time<20 ms
Rated output voltage1P/N/PE, 220V / 230V
Rated output frequency50Hz
Rated output current14A / 13.5A23A / 22A
THDv<2% (@ linear load)

Input AC (Grid side)

Input voltage range187V~265V
Maximum input current20.5A / 20A25A / 23.5A31.5A / 30A34.5A / 33A34.5A / 33A
Frequency range45-55Hz / 55-65Hz

Output AC (Grid side)

Rated output power3kW3.6kW4kW5kW6kW
Maximum apparent output power3.3kVA4kVA4.4kVA5.5kVA6.6kVA
Rated grid voltage1P/N/PE, 220V / 230V
Rated grid frequency50Hz
Rated grid output current13.7A / 13.1A16.4A / 15.7A20.9A / 20A22.8A / 21.7A27.3A / 26.1A
Maximum output current15.1A / 14.4A18A / 17.3A23A / 22A25.1A / 23.9A30A / 28.7A
Power factor>0.99 (-0.8~+0.8 adjustable)
THDi<2%

Performance data

Maximum efficiency97.1%
EU efficiency96.5%
ProtectionDC reverse-polarity protection, Short circuit protection, Output over current protection, Surge protection (DC Type II / AC Type II), Ground fault monitoring, Integrated AFCI (DC arc-fault circuit protection, Activation required), Protection class/Over voltage category (I/II)
DC connectionMC4 connector
AC connectionQuick connection plug
Display7.0″ LCD color screen display
CommunicationRS485, Wi-Fi, GPRS (Optional)

General data

Operating temperature range-25ºC~60ºC
Ingress protectionIP65
Cooling conceptNatural cooling
Maximum operation altitude3000 m
CertificationsEN61000-6-1/2/3/4, IEC/EN 62109-1/2, IEC61140, CEI 0-21
Weight20 kg
Dimensions (WxDxH)420x235x450 mm
Scroll to Top